Standard Test Method for Hot-Surface Ignition Temperature of Dust Layers
Automatische name übersetzung:
Standard Test Method for Hot-Oberfläche die Zündtemperatur der Staubschichten
NORM herausgegeben am 1.10.2013
Bezeichnung normen: ASTM E2021-09(2013)
Anmerkung: UNGÜLTIG
Ausgabedatum normen: 1.10.2013
SKU: NS-43991
Zahl der Seiten: 10
Gewicht ca.: 30 g (0.07 Pfund)
Land: Amerikanische technische Norm
Kategorie: Technische Normen ASTM
Keywords:
dust layer ignition, hot surface ignition, ignition temperature, ICS Number Code 13.230 (Explosion protection)
Significance and Use | ||||||||||||||||
5.1 This test method is applicable to dusts and powders, and provides a procedure for performing laboratory tests to evaluate hot-surface ignition temperatures of dust layers. 5.2 The test data can be of value in determining safe operating conditions in industrial plants, mines, manufacturing processes, and locations of material usage and storage. 5.3 Due to variation of ignition temperature with layer thickness, the test data at one thickness may not be applicable to all industrial situations (see
5.4 This hot plate test method allows for loss of heat from the top surface of the dust layer, and therefore generally gives a higher ignition temperature for a material than Test Method E771, which is a more adiabatic system. 5.5 This test method for dust layers generally will give a lower ignition temperature than Test Method E1491, which is for dust clouds. The layer ignition temperature is determined while monitoring for periods of minutes to hours, while the dust cloud is only exposed to the furnace for a period of seconds. 5.6 Additional information on the
significance and use of this test method may be found in Ref.
1.1 This test method covers a
laboratory procedure to determine the hot-surface ignition
temperature of dust layers, that is, measuring the minimum
temperature at which a dust layer will self-heat. The test consists
of a dust layer heated on a hot plate.2,3
1.2 Data obtained from this test method provide a relative measure of the hot-surface ignition temperature of a dust layer. 1.3 This test method should be used to measure and describe the properties of materials in response to heat and flame under controlled laboratory conditions and should not be used to describe or appraise the fire hazard or fire hazard risk of materials, products, or assemblies under actual fire conditions. However, results of this test method may be used as elements of a fire risk assessment that takes into account all of the factors that are pertinent to an assessment of the fire hazard risk of a particular end use product. 1.4 The values stated in SI units are to be regarded as standard. No other units of measurement are included in this standard. 1.5 This standard does not
purport to address all of the safety concerns, if any, associated
with its use. It is the responsibility of the user of this standard
to establish appropriate safety and health practices and determine
the applicability of regulatory limitations prior to use.
Standard Test Method for Minimum
Autoignition Temperature of Dust Clouds Standard Terminology Relating to Hazard
Potential of Chemicals Standard Test Method for Spontaneous
Heating Tendency of Materials (Withdrawn 2001) |
Wollen Sie sich sicher sein, dass Sie nur die gültigen technischen Vorschriften verwenden?
Wir bieten Ihnen Lösungen, damit Sie immer nur die gültigen (aktuellen) legislativen Vorschriften verwenden könnten.
Brauchen Sie mehr Informationen? Sehen Sie sich diese Seite an.
Letzte Aktualisierung: 2024-12-23 (Zahl der Positionen: 2 217 157)
© Copyright 2024 NORMSERVIS s.r.o.