Wir benötigen Ihre Einwilligung zur Verwendung der einzelnen Daten, damit Sie unter anderem Informationen zu Ihren Interessen einsehen können. Klicken Sie auf "OK", um Ihre Zustimmung zu erteilen.
Standard Test Method for Using a Cone Calorimeter to Determine Fire-Test-Response Characteristics of Insulating Materials Contained in Electrical or Optical Fiber Cables
Automatische name übersetzung:
Standard Test Method for Mit einem Cone-Kalorimeter zu Brandversuchen Ansprechverhalten der Dämmstoffe in elektrische oder optische Glasfaserkabel Enthalten Bestimmen
NORM herausgegeben am 1.4.2011
Bezeichnung normen: ASTM D6113-11
Anmerkung: UNGÜLTIG
Ausgabedatum normen: 1.4.2011
SKU: NS-33841
Zahl der Seiten: 20
Gewicht ca.: 60 g (0.13 Pfund)
Land: Amerikanische technische Norm
Kategorie: Technische Normen ASTM
Ignitability and burning behaviour of materials and productsInsulating materials in generalFibres and cables
Keywords:
cable, cone calorimeter, electrical cable, electrical insulation, fire, fire-test response, heat release, heat release rate, optical fiber cable, oxygen consumption calorimetry, smoke obscuration, Cone calorimeter, Electrical fiber cable, Electrical insulating materials, Fire-test response, Heat release, Insulating materials, Optical fiber/cable/conduit, Smoke obscuration, ICS Number Code 13.220.40 (Ignitability and burning behaviour of materials and products)
Significance and Use | ||||||||||||||||||||||||||||||||
This test method is used to determine the heat release rate and a number of other fire-test-response characteristics as a result of exposing insulating materials contained in electrical or optical cables to a prescribed heating flux in the cone calorimeter apparatus. Quantitative heat release measurements provide information that is potentially useful for design of electrical or optical cables, and product development. Heat release measurements provide useful information for product development by giving a quantitative measure of specific changes in fire performance caused by component and composite modifications. Heat release data from this test method will not be predictive of product behavior if the product will not spread flame over its surface under the fire exposure conditions of interest. The fire-test-response characteristics determined by this test method are affected by the thickness of the material used as test specimen, whether as a plaque or as coating on a wire or cable. The diameter of the wire or cable used will also affect the test results. A radiant exposure is used as an energy source for this test method. This type of source has been used for comparison with heat release rate and flame spread studies of insulating materials constructed into cables when burning in a vertical cable tray configuration (Test Methods D5424 and D5537) (2-9). No definitive relationships have been established. The value of heat release rate corresponding to the critical limit between propagating cable fires and non-propagating fires is not known. This test method does not determine the net heat of combustion. It has not been demonstrated that this test method is capable of predicting the response of electrical or optical fiber cables in a full scale fire. In particular, this test method does not address the self-extinguishing characteristics of the cables in a full scale fire. |
||||||||||||||||||||||||||||||||
1. Scope | ||||||||||||||||||||||||||||||||
1.1 This is a fire-test-response standard. 1.2 Several fire-test-response characteristics, including the time to sustained flaming, heat release rate, total heat released, effective heat of combustion, and specific extinction area; are measured or calculated by this test method at a constant radiant heating flux. For specific limitations see also 5.7 and Section 6. 1.3 The tests are conducted by burning the electrical insulating materials contained in electrical or optical fiber cables when the cable test specimens, excluding accessories, are subjected to radiant heat. 1.4 The values stated in SI units are to be regarded as the standard. The values given in parentheses are for information only. 1.5 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability or regulatory limitations prior to use. For specific precautionary statements, see Section 7. 1.6 This standard measures and describes the response of materials, products, or assemblies to heat and flame under controlled conditions, but does not by itself incorporate all factors required for fire hazard or fire risk assessment of the materials, products or assemblies under actual fire conditions. 1.7 Fire testing is inherently hazardous. Adequate safeguards for personnel and property shall be employed in conducting these tests. |
||||||||||||||||||||||||||||||||
2. Referenced Documents | ||||||||||||||||||||||||||||||||
|
Historisch
1.1.2010
Historisch
1.5.2014
Historisch
1.6.2010
Historisch
1.3.2010
Historisch
1.11.2013
Historisch
1.3.2010
Wollen Sie sich sicher sein, dass Sie nur die gültigen technischen Vorschriften verwenden?
Wir bieten Ihnen Lösungen, damit Sie immer nur die gültigen (aktuellen) legislativen Vorschriften verwenden könnten.
Brauchen Sie mehr Informationen? Sehen Sie sich diese Seite an.
Letzte Aktualisierung: 2024-11-01 (Zahl der Positionen: 2 208 817)
© Copyright 2024 NORMSERVIS s.r.o.